EN 12464-1 standard: illuminance levels room by room

How to read the EN 12464-1 standard by visual task and find the illuminance, uniformity and UGR expected in each workplace.

Luminance ConsultingProfessional lighting design office

4 min read

Break area and office corridor lit by LED luminaires

The project owner opens the standard and looks for the office line. There he finds data entry, writing, reading, technical drawing, filing and the reception desk, each with its own value. The difficulty of the EN 12464-1 standard starts there.

What the EN 12464-1 standard covers and what it does not

The EN 12464-1 standard deals with the lighting of indoor workplaces. For each visual task, it sets the characteristics the installation must reach so that people can work in good conditions of visual comfort and performance.

Its scope stops at clear boundaries. Emergency lighting falls under the EN 1838 standard. Outdoor workplaces fall under part 2, EN 12464-2. Sports facilities fall under the EN 12193 standard and roads under the EN 13201 series. Looking for a stadium or a forecourt in part 1 leads to applying the wrong requirement.

Reasoning by visual task, not by room name

The standard classifies requirements by activity. A single room can therefore fall under several lines: a room that hosts computer data entry, document sorting and a reception desk combines three requirements in the same volume.

The method consists of describing what the occupant does, then looking up the corresponding activity in the table. The useful questions concern the fineness of the detail to be perceived, the contrast of the task and the length of time it is carried out.

Two adjustments then correct the line found. The age of the occupants weighs on the need: the amount of light required to perceive the same detail increases over the years. How critical an error is also weighs, because an inspection where a missed defect goes out to the customer justifies going up one step from the base value in the table.

The four associated criteria: illuminance, uniformity, UGR, colour rendering

Each line of the standard’s table carries four values. Maintained illuminance gives the level, uniformity guarantees its distribution, UGR limits discomfort glare and the colour rendering index determines the perception of colours.

Room or activity

Maintained illuminance

UGR limit

Colour rendering

Writing, typing, reading, data processing

500 lux

19

Ra ≥ 80

Meeting and conference room

500 lux

19

Ra ≥ 80

Reception desk

300 lux

22

Ra ≥ 80

Archives

200 lux

25

Ra ≥ 80

Corridors and circulation routes

100 lux

28

Ra ≥ 40

Stairs

100 lux

25

Ra ≥ 40

The current version of the standard adds further criteria, notably on the illuminance of walls and ceilings and on cylindrical illuminance, which deals with the perception of faces in the space.

Task area, immediate surrounding area, background

The standard divides the surface into three successive rings, each with its own requirement. The task area holds the activity itself. The immediate surrounding area is the band around it. The background covers the surface beyond.

Zone

Extent

Minimum uniformity

Task area

Surface where the activity takes place

0.60

Immediate surrounding area

Band at least 0.5 metre wide around the task area

0.40

Background

Band at least 3 metres wide adjacent to the surrounding area

0.10

The illuminance of the immediate surrounding area follows a decreasing scale relative to the task area, and that of the background in turn relates to the surrounding area. This division explains why a workstation can be compliant in a room that looks dark, and why the reverse situation is just as common.

Maintained illuminance, not illuminance when new

The values of the standard are maintained illuminances. The average over the task area must not fall below this value before the next maintenance operation, which means sizing the installation above it at commissioning.

The gap between the two depends on the maintenance factor, which combines the lumen depreciation of the sources, their survival rate, dirt on the luminaires and dirt on the room surfaces. An installation sized without a margin is compliant on the day of acceptance and falls below the requirement well before the end of its useful life.

Voluntary standard and regulatory obligation: how they fit together

The EN 12464-1 standard is voluntary. It becomes contractual as soon as a technical specification or a contract refers to it, and the acceptance of the works is then carried out against it.

The enforceable framework comes from the French Labour Code, whose articles on lighting set minimums far below the comfort levels of the standard: 40 lux for indoor circulation routes, 60 lux for stairs and warehouses, 120 lux for workrooms, changing rooms and toilets, 200 lux for windowless rooms used for permanent work.

These minimums are a floor, not a design target. The employer remains bound to adapt the lighting to the real activity, and a visual inspection station lit at 120 lux respects the letter of the code while putting the operator in difficulty.

Checking the compliance of an existing room

The check follows four steps. Identify the dominant visual task of each zone and the associated line of the standard. Measure the illuminance on the specified grid of points, at the height of the working plane. Calculate the uniformity from the values recorded. Finally, compare the result with the maintained illuminance, not with a theoretical value when new.

This comparison is the core of an on-site lighting audit. When the gap is confirmed, a photometric study determines the layout that brings the room back within the values, before any equipment is bought. The benchmarks by type of room are gathered on our page dedicated to the compliance of lighting installations.

On the equipment side, luminaires for workspaces and general-purpose industrial luminaires cover most lines of the standard’s table.

To have the compliance of your premises checked, request a visit and measurements from the contact page.

Related articles

More articles, those in the same category first.

View all articles
  • Workshop aisle lined with workstations, lit by lines of LED luminairesStandards and compliance

    Lighting at work: what the French Labour Code requires

    Enforceable minimum values, the employer's obligations, how they fit with the EN 12464-1 standard: the legal framework for workplace lighting.

    Luminance ConsultingProfessional lighting design office

    5 min read

  • Office corridor lit by recessed LED luminairesStandards and compliance

    OPERAT declaration: which lighting data to submit

    How to reconstruct and declare lighting consumption on OPERAT when the building has no dedicated sub-metering.

    Luminance ConsultingProfessional lighting design office

    5 min read

  • Sports hall lit by LED luminaires, view of the courtStandards and compliance

    EN 12193 standard: understanding sports lighting classes

    Classes I, II and III of the EN 12193 standard: how to place your sports facility and anticipate the illuminance level to be reached.

    Luminance ConsultingProfessional lighting design office

    5 min read