An open-plan office renovated last year keeps generating the same complaints: reflections on screens at the end of the day, discomfort when looking up, eye strain near the facades. Yet lux meter readings give compliant values on the work surfaces. Illuminance level alone is not enough to make a space comfortable.
The standard criteria applicable to office spaces
The EN 12464-1 standard sets four criteria for each visual task, to be read together: maintained illuminance on the task area, uniformity, glare limitation through the UGR index, and colour rendering. Keeping the first while forgetting the other three produces exactly the situation described above.
Space | Maintained illuminance | Maximum UGR |
|---|---|---|
Writing, typing, reading, data processing | 500 lux | 19 |
Meeting room | 500 lux | 19 |
Reception, reception desk | 300 lux | 22 |
Archives | 200 lux | 25 |
Circulation areas and corridors | 100 lux | 28 |
These values are requirements to be maintained throughout the life of the installation, not values when new. A colour rendering index of at least 80 is expected in spaces occupied for long periods. The lighting compliance page explains how these standard requirements fit with regulatory obligations.
Illuminance on the work surface and in the immediate surroundings
The standard works in concentric zones. The task area receives the main requirement. The immediate surrounding area, a band around the task, receives a lower requirement linked to the first. The background completes the whole with an even lower requirement.
This gradation avoids overly sharp contrasts in the field of view. A properly lit workstation in the middle of a dark floor forces the eye to adapt constantly, which is more tiring than a slightly lower but even level. In practice, complaints often come from workstations at the edge of the floor.
The work plane sits at the actual height of the desks. A simulation calculated at floor level gives values unrelated to the task being performed.
UGR: linking the index to occupant complaints
The UGR index quantifies the discomfort glare produced by the luminaires in an observer's field of view. The lower the value, the less noticeable the discomfort. The threshold of 19 applies to screen-based workstations as well as to meeting rooms.
The discomfort shows up as very concrete symptoms: needing to look away from the ceiling, squinting, headaches at the end of the day, a working position altered to avoid a luminaire. These signs amount to a diagnosis when they are concentrated on certain workstations and not on others.
One point is worth knowing before any order: UGR depends on the room, the layout grid and the position of the observer, not just on the luminaire. A value read on a product data sheet describes a conventional reference room.
Screens, reflections and workstation positioning
Screen reflection depends on three elements: the luminance of the luminaire, its position relative to the workstation and the orientation of the screen. A well-lit floor can become uncomfortable simply because the desks were turned during a refit, without the lighting having moved.
A few rules limit the problem: avoid luminaires placed in the line of sight behind the screen, orient workstations perpendicular to glazed facades, choose optics whose luminance remains controlled at the angles where people look. The position of the furniture is part of the lighting project, just like the choice of luminaires.
The surfaces on the floor also play a part. A very light, glossy work surface reflects the luminaire back to the eye, dark furniture deepens contrasts. These choices are usually made with the fit-out contractor, without the lighting being considered, even though they change the perceived result as much as a change of optic.
Meeting rooms and video conferencing
A meeting room used for video conferencing changes in nature. The visual task is the faces, so vertical illuminance matters, not just the table plane. Purely overhead lighting hollows out the eye sockets and hardens features on camera.
The solution involves a vertical illuminance component directed towards the participants, glare limitation along the camera axis and a uniform colour temperature throughout the room. The controls must make it possible to switch from a standard meeting scene to a video conference scene without technical intervention. The ranges of luminaires for meeting rooms cover these configurations.
Daylight and areas close to the facades
Workstations near the glazing receive a contribution that varies during the day and across the seasons. They combine two difficulties: a strong contrast between the window and the inside of the floor, and possible discomfort in the middle of the day when the sun is low.
The answer combines solar shading, control by zones parallel to the facades and dimming linked to a daylight sensor. The split of control zones is decided at the same time as the luminaire layout, otherwise reworking it becomes costly.
The question also arises at the end of the day in winter, when artificial lighting takes over very early and the glazing becomes dark surfaces. The contrast is then reversed, and an installation set up only for summer conditions can disappoint from November onwards.
Presence detection and dimming in open-plan offices
Detection on an open floor calls for adjustment, not just equipment. A time delay that is too short causes annoying switch-offs for a motionless occupant, one that is too long cancels out the expected saving. A low standby level, rather than a complete switch-off, avoids the dark corridor effect at the periphery.
These settings also feed into the consumption monitoring expected under the framework covered in our article on the French tertiary decree applied to office lighting. On the equipment side, luminaires for offices and open-plan spaces incorporate the usual control interfaces, and our lighting solutions by sector present the related use cases.